Journal of System Simulation ›› 2017, Vol. 29 ›› Issue (1): 170-180.doi: 10.16182/j.issn1004731x.joss.201701023

Previous Articles     Next Articles

Optimization for Alternative Schemes of Black Start Power Sources Considering Water Reserve of Hydropower Station

Gu Xueping1, Liu Wenxuan1, Wang Jiayu1, Jia Jinghua2   

  1. 1. Department of Electric Power Engineering, North China Electric Power University, Baoding 071003, China;
    2. Hebei Power Dispatch and Communication Center, Shijiazhuang 050021, China
  • Received:2016-02-22 Revised:2016-05-19 Online:2017-01-08 Published:2020-06-01

Abstract: An optimization method was proposed to determine alternative schemes of the hydropower black start sources, by considering water reserve constraints. A pumped storage power station was employed to crank some thermal units close to the pumped storage and was with good start-up performance. The restarted thermal units were used as power sources for subsequent restoration instead of the pumped storage units. The reliability of restoring units, the total capacity of selected units and units' node importance in network were defined as objective functions of the optimization problem. The immune algorithm was employed to search for the Pareto optimal solution set of the feasible schemes. The grey correlation model was applied to identify satisfactory solution from the solution set. The effectiveness of the proposed method was validated by simulation results.

Key words: power system restoration, black start power source, reservoir storage, alternative power source