Journal of System Simulation ›› 2017, Vol. 29 ›› Issue (6): 1284-1289.doi: 10.16182/j.issn1004731x.joss.201706017

Previous Articles     Next Articles

State Feedback Control of Hybrid Active Power Filter

Wang Yunjian1, Liu Xiaoyun1, Zhang Rongzhi2, Xue Nana1   

  1. 1. School of Electrical Engineering and Automation, Henan Polytechnic University, Jiaozuo 454000, China;
    2. CPI Henan Power Overhaul Engineering Co. Ltd., Zhengzhou 450000, China
  • Received:2015-07-21 Revised:2015-10-08 Online:2017-06-08 Published:2020-06-04

Abstract: According to the current tracking of active power filter, a state feedback control strategy was applied to three-phase shunt hybrid active power filter system, replacing popular PID controller, to overcome the drawbacks of the PID controller, such as big overshoot, error compensation etc.. The mathematical model was established and the feedback control law was derived based on the topological structure of hybrid active power filter selected. Moreover, the current detection used ip-iq detection algorithm while the stability of capacitor voltage in DC side used PI control. MATLAB/Simulink was applied to simulate the HAPF system, comparing with the traditional PI hysteresis comparison control method. The results show that the state feedback control algorithm can obviously improve tracking performance of the system, and improve the harmonic compensation effect of APF.

Key words: active power filter, state feedback, current tracking control, harmonic compensation

CLC Number: