Journal of System Simulation ›› 2018, Vol. 30 ›› Issue (4): 1572-1580.doi: 10.16182/j.issn1004731x.joss.201804045

Previous Articles     Next Articles

Comparative Study of Photovoltaic Islanding Detection Based on SMS and AFD

Yu Yunjun1, Zhong Guoying1, Fan Ruixiang2, Ji Qingzhao2, Zhu Jianyong3   

  1. 1. Nanchang university, School of Information Engineering, Nanchang 330031, China;
    2. Jiangxi Electric Power Science Research Institute, Nanchang 330096, China;
    3. Huadong Jiaotong University, Electrical Engineering College, Nanchang 330096, China
  • Received:2016-05-18 Revised:2016-06-30 Online:2018-04-08 Published:2019-01-04

Abstract: There are many islanding detection methods, especially the active islanding detection method. It is difficult to choose the best method among so many active islanding detection methods in practice. In this paper, the non-detection zone (NDZ), detection speed and their effect to power quality of slide-mode frequency shift (SMS) method and active frequency drift (AFD) were researched. The results show that SMS is superior to AFD at the aspect of the effect on power quality when they have same NDZ. While the detection speed of SMS has big difference under different parameters. The Islanding detection model was built on Matlab/Simulink. The experimental results show the correctness of theoretical analysis.

Key words: SMS, AFD, NDZ, power quality, detection speed

CLC Number: